@thesis{thesis, author={Rahmananda Dimas Arsy and Susanto Djoko}, title ={ANALISA JATUH TEGANGAN DAN PERBAIKAN FAKTOR DAYA PADA JARINGAN TEGANGAN MENENGAH 20 KV PENYULANG HOPAX DI GARDU INDUK NGORO}, year={2016}, url={http://156.67.221.169/1057/}, abstract={The development of industrial and household current will certainly affect the use of electrical load. The magnitude of the load demand and away lies the burden of plants lead to problems in the distribution of electrical power mainly voltage drop problem. For industrial customers, the majority of the load is inductive, certainly have the potential to experience a voltage drop greater because if the low power factor, the current electrical load supplied from PLN getting bigger, causing the voltage drop across the channel. To reduce the voltage drop across the feeder channel Hopax required voltage drop analysis methods as well as power factor improvement on one load. The magnitude of the voltage drop at the end of the feeder Hopax to 2.514% of working days and holidays amounting to 0.433%. In accordance with SPLN 72 1987, the voltage drop is still within tolerable limits PT PLN (Persero). After making the power factor improvement on one load to the shunt capacitor, the voltage drop at the end of the line becomes 2.453% on weekdays and 0,375% on holidays. Installation of capacitor is one effective way to reduce the voltage drop across the medium voltage networks is in an industrial area.} }