@thesis{thesis, author={Basri Hasan and FIRMANSYAH IQBAL}, title ={UPAYA MENGATASI JATUH TEGANGAN PADA SALURAN DISTRIBUSI TEGANGAN RENDAH PT PLN (PERSERO) DISTRIBUSI JABAR DAN BANTEN AREA CIREBON KOTA}, year={2015}, url={http://156.67.221.169/1278/}, abstract={In the distribution of electricity from the power source to the consumer that far apart always suffered losses in the form of loss - loss of power loss and voltage that results in a voltage drop large enough to result in low voltage thank particularly different at the end of the channel. The voltage on the low voltage network in the set of electric power system by PT PLN (Persero) is a 230 Volt / 400 Volt. In the operating voltage on the distribution system must be keep it meet that standard operating voltage Vop 0.9 ? Vnom ? 1.05 Vnom. For system 230 Volt / 400 Volt, the operating voltage phase - neutral must be kept constantly on the value of 198 Volts ? Vop ? 231 Volts. In fact its on the field much stress, especially at the end - the end of the voltage network under of 198 volts (standard), it is necessary to repair the voltage on the JTR. Repair the voltage on the low voltage distribution substations can be implemented by installing inserts, replacing the wire conductor cross section with a larger cross section of the wire, fix the conductor wire connection at the connection point, leads without load, and the use of capacitors (shunt).} }