@thesis{thesis, author={Iman M. Soadrul and Widyastuti Christine}, title ={Analisis Kinerja PLTS On-Grid 200 kWp di Bandar Udara Sultan Muhammad Salahudin Bima}, year={2019}, url={http://156.67.221.169/1447/}, abstract={In a 3 phase system, transformer load imbalances occur very often especially in low voltage distrubution systems. Because of the many additions to electrical loads that do not pay attention to load imbalances on the R, S, T side that should be designed is balanced, this is because there are costumers who want to add to the burden. Load imbalanced on transformer phases results in losses in the transformer and power system, if left unchecked it will cause damage to the transformer. Therefore the problem of load imbalance must be minimized in order to reach the optimum performance of the transformer. From the result of the load measurements on the TG 08 distrubution substation at PT.PLN Cikokol Area which was carried out on April 18, 2019 at 13.00 19.45 the calculation of the imbalance percentage of transformer loading at 13.00 and 19.45 before loading was carried out at 49% and 38%. Then for the loading imbalance at 13.00 and 19.45 before load equalization 27,36% and 30,67%. After load equalization simulation, the percentage of transformer loading at 13.00 and 19.45 is 45% and 37,99% ang the percentage of load imbalance is 0%.} }