@thesis{thesis, author={Pramono Tri Joko and Riza Kurniawan Mochammad}, title ={ANALISA PEMINDAHAN BEBAN UNTUK MENGURANGI SUSUT DAYA PADA JARINGAN DISTRIBUSI DI PENYULANG PANDEAN LAMPER 16 PT. PLN (PERSERO) UP3 AREA SEMARANG}, year={2022}, url={http://156.67.221.169/5350/}, abstract={Due to the length of the conductor line in a feeder, power losses occur in the distribution network in the Pandean Lamper 16 feeder. A loss of electrical power in the delivery of electrical energy is actually something that cannot be prevented. However, if it is not adequately handled, the energy loss that happens during the distribution and distribution of electrical energy is a waste of energy. using comparative quantitative approaches, where the goal of the study is to quantify the degree to which a variable differs between two groups. Based on study of the computation of the Pandean Lamper feeder's 16, 70, and 240 mm2 with a conductor length of approximately 13 km, the power loss at morning load is 2.00%, and at night load is 1.08%. The power loss in the distribution system is typically between 5 and 10%, and using the load transfer method can reduce it by up to 1.86% at morning load and 0.95 percent at night.} }