@thesis{thesis, author={Kurniawan Rahmat and Pasra Nurmiati}, title ={UNJUK KERJA KABEL SOLAR 0,6/1 KV DENGAN PENGUJIAN TAHANAN KONDUKTOR, KUAT TARIK DAN HOT SET ISOLASI PADA PT. VOKSEL ELECTRIC Tbk.}, year={2022}, url={http://156.67.221.169/5373/}, abstract={Solar cables are very influential on the safety of the installation of Solar Power Plants (PLTS). Damage to components and even fire can occur in PLTS installations, this is because the conductor resistance does not comply the IEC 60228 standard and the insulation strength against the hot set test does not comply the EN 60811-507 standard. In addition, the tensile strength of the solar cable that does not comply the EN 60811-501 standard can affect the time of cable deployment which causes the insulation to break and makes the cable life shorter. From the test results, the VOKSEL type cable has a conductor resistance value of 4.92?/km, with an average tensile strength of 14.13 N/mm2 and an average elongation of the hot set test of 16.63%. The HENGTONG type cable has a conductor resistance value of 3.20?/km, an average tensile strength of 14.84 N/mm2 and an average elongation of the hot set test of 47.6%. Meanwhile, APAR-UNICAB cable has a conductor resistance value of 5.58 ? /km and an average tensile strength of 12.64 N/mm2. VOKSEL & HENTONG type cables have met the standards of the three tests, namely IEC 60228 standard for conductor resistance, EN 60811-501 standard for tensile strength test, and EN 60811-507 standard for hot set test. Meanwhile, the APAR-UNICAB type cable has not met the IEC 60228 standard for the conductor resistance test and the EN 60811-507 standard for the hot set test.} }