@thesis{thesis, author={Muhammad Ryan Ranus Fahran La Ode and Sari Dewi Purnama}, title ={ANALISIS REKONFIGURASI JARINGAN DISTRIBUSI 20 KV PADA GARDU INDUK TELUK NAGA DI UP2D BANTEN}, year={2022}, url={http://156.67.221.169/5383/}, abstract={In terms of quality and efficiency, this voltage is strongly influenced by the presence of voltage drops and electrical power losses so that the level of reliability in the distribution network decreases, which is not in accordance with SPLN 1: 1995 Voltage Drop +5% & -10% and SPLN 72: 1987 Power loss ?10% . The method used to increase distribution in the 20 kV distribution network is by reconfiguring the load transfer from one feeder to another using the LBS (Load Break Switch) component. This reconfiguration simulation was carried out with the Digsilent application. The data used were obtained from UP2D Banten PT. PLN (Persero) at the Teluk Naga Substation 20 kV by looking at the highest feeder maximum load current value. The feeder that will be reconfigured is the Jarum Feeder. Based on the results of research using Digsilent simulation. The first reconfiguration of the percentage of voltage drop obtained is 2%, the percentage of power losses is 6.5%. The second reconfiguration of the percentage of voltage drop obtained is 1.5%, the percentage of power losses is 6.61% and. The third reconfiguration of the percentage of voltage drop obtained is 2%, the percentage of power losses is 8.3%. The fourth reconfiguration of the percentage of voltage drop obtained is 2%, the percentage of power losses is 14.58%. The fifth reconfiguration of the percentage of voltage drop obtained is 2%, the percentage of power losses is 14.61%.} }