@thesis{thesis, author={Tambunan Juara Mangapul and WANDRA YAJIZ}, title ={STUDI PERHITUNGAN ARUS BOCOR LIGHTNING ARRESTER PADA BAY TRAFO 3 DI GARDU INDUK 150kV SERPONG TANGERANG SELATAN}, year={2022}, url={http://156.67.221.169/5395/}, abstract={Lightning Arrester is a device that plays a role in ensuring the quality and reliability of power supply to consumers. The surja arrester plays an important role in limiting the switching and lightning surgery that flows from the substation to the ground. The data analysis method used is a qualitative method, then the data is processed, analyzed, and evaluated. So the percentage value of leakage current for the R phase lightning arrester is 73%, while the S phase is 716% and for the T phase it is 316%. For the leakage current percentage value in the R phase lightning arrester of 73% this shows that the value is below ?90% which means that the recommendation for the R phase lightning arrester is to be retested 1 yearly. While the results of the calculation of the percentage of leakage current of the S and T phase lightning arresters of 716% and T phases of 216%, the value is far above ?100% which means that the recommendation for the S and T phase lightning arresters must be replaced in phaseS S and T in the bay of Transformer 3 of the Serpong Substation in February 2022.Based on the results of LCM (leakage current measurement) measurements carried out at the Serpong Bay 150kV Transformer 3 Substation on February 24, 2022,obtained the value of the leakage current result in the lightning arrester phase R, namely 110 (?), phase S 1074 (?) and phase T 504 (?).} }