@thesis{thesis, author={Radhitya Muhammad Rifqy and Suyanto Heri}, title ={ANALISIS SENSITIVITAS TEGANGAN BUSBAR PADA SIMULASI SUBSISTEM TENAGA LISTRIK ACEH MENGGUNAKAN PERANGKAT LUNAK DIGSILENT}, year={2023}, url={http://156.67.221.169/5746/}, abstract={The Aceh power subsystem is highly vulnerable to voltage instability problems. This is due to radial network topology and lack of large generators that can compensate for changes in reacive power. Analysis such as simulation of power flow and voltage stability is needed to determine how significant for voltage problems can be to cause more considerable disturbances such as Voltage Collapse. The static voltage stability analysis method using Voltage Busbar Sensitivity approach is carried out with Digsilent software to calculate the busbar voltage sensitivity ratio (dV/dQ) for each scenario of the operating conditions the Aceh power subsystem, from normal to worst conditions and mitigation planning. Based on the simulation results, in the absence operations of Naganraya steam powerplant units, the shunt capacitor operating is only able to improve the operational voltage for each substation in the Aceh power subsystem at the range of 145 -153 kV, but it does not significantly reduce the value of the busbar voltage sensitivity ratio. The combined operating conditions of the 150 kV Aceh subsystem backbone looping and the North Sumatra ? Aceh 275 kV interconnection can reduce the value of busbar voltage sensitivity ratio (dV/dQ) at each substation in the Aceh power subsystem, even the highest is only around 0.001 p.u/MVAR. Then busbar voltage sensitivity ratio data is expected to help power system operators to avoid the potential for Voltage Collapse in operating the power system.} }