@thesis{thesis, author={Hidayat Wildan and Suyanto Hery}, title ={ANALISIS SISTEM LIGHTNING ARRESTER DAN PENTANAHAN TERHADAP SAMBARAN PETIR PADA TRAFO UNIT 2 PLTM LAMBUR}, year={2023}, url={http://156.67.221.169/5767/}, abstract={Lightning Arrester is a channel guard against lightning strikes so that the Lightning Arrester isolation and grounding must be in good condition in order to protect the generation equipment. The PLTM Lambur transformer is a vital piece of equipment where safety must be maintained. On this basis, lightning arresters must comply with standards by testing insulation resistance and earthing resistance. In the insulation resistance test at the bottom-ground points the values were 0.2 M?, 0.07 M? and 0.4 M?, at that point they did not meet the minimum value standard (> 1 M? / 1 kV) because the mount on the lightning arrester was cracked and needed replacement. After replacing the lightning arrester holder, the results of testing the insulation resistance at the bottom?ground point at the R phase of 76.8 M?, the S phase is 141 M?, and the T phase is 96.4 M?, it can be seen that the insulation resistance at the bottom-ground point is already in good condition. well and above the minimum standard value. The results of the grounding resistance test, namely the phases R 7 ?, S 7 ?, and T 6 ? based on the value of the insulation resistance, do not meet the standard where the value is > 5 Ohm, and grounding roads must be added so that the value meets the standard, so that after adding grounding rods the value in phase R 1?, S1 ?, and T 1? based on the insulation resistance value meets the standard where the value is < 5 Ohm.} }