@thesis{thesis, author={Athallah Ilham and Senen Adri}, title ={PENGUJIAN DAN ANALISIS DISTRIBUSI TEGANGAN ISOLATOR T. 352 SUTET 500 kV TASIK - DEPOK DALAM KEADAAN BERTEGANGAN}, year={2023}, url={http://156.67.221.169/5945/}, abstract={High-voltage overhead lines are part of the electric power transmission system, which plays a very important role in maintaining quality and reliability to distribute electricity with very large capacities. In the distribution of electric power the quality of the insulator will affect the stability of the electricity, if the condition of the insulator is not good it will result in the distribution of electric power being often disrupted by phase to ground faults. The quality of the insulator is reduced due to corrosiveness, pollution and flash over. Visual testing of high-voltage overhead line insulators using a puncture test is a type of Level 2 inspection for SUTT/SUTET maintenance. Visual inspection in the field of insulator T. 352 SUTET 500 kV Tasik - Depok provides measurement data results, with these results can be analyzed using quantitative methods. The results of the test analysis show that the insulator T. 352 SUTET 500 kV Tasik - Depok has a decrease in the voltage distribution of 48.85% from chip 20 to chip 21 and the value has not changed after experiencing a decrease in the voltage distribution of more than 30% for chips 22 and 23 with a total 3 pieces of insulator damage.} }