@thesis{thesis, author={Ispranyoto Edy and Manalu Abriana V. W. R.}, title ={ANALISIS TEGANGAN SENTUH DAN TEGANGAN LANGKAH PADA SISTEM PEMBUMIAN DI GARDU INDUK PLUMPANG}, year={2018}, url={http://156.67.221.169/674/}, abstract={Substation as one part of the system of electric power that plays a role in transmitting electric power from the plant toward the load, so that the condition must be determined safe. But substation has the potential of experiencing the disorder poses flow short circuit which can endanger the surrounding equipment and human condition, then Substation Plumpang wear system ground as its protector. Ground at the substation is said to be good if the value of resistance less than 1 ?. Grounding on Substation Plumpang of 0.12 ?. To find out the step voltage and touch voltage which occurs still in the safe limit then it needs to be compared to the touch voltage and step voltage permitted according to IEEE std 80-year 2000. The touch voltage and step voltage maximum amount of 418.49 V and of 177.66 V that occurred in Substation Plumpang.} }