@thesis{thesis, author={Hariyanto Agung and Wibowo Tresno}, title ={ANALISIS PENGGUNAAN TRAFO PEMAKAIAN SENDIRI UNTUK MEMENUHI KEBUTUHAN BEBAN DI KLUSTE}, year={2018}, url={http://156.67.221.169/689/}, abstract={Generating becomes a vital object, where special supervision is needed for each existing equipment. The use of assistive devices as a labor generator must also be taken intoaccount. Transformer is one of the functions used to supply load loads below it. If the transformer is burdened with 107%, it can only work within 6 hours per day because the temperature of the hotspot reaches 110 ° C. The help scale cannot work properly. If so, the plant will be disturbed. To improve the reliability of the Generating system, an explanation of the 200kVA transformer unit was made. In this study, the maximum loading value on the transformer will be obtained at a hot temperature which will be analyzed at the maximum level it can work in excess conditions. Load taking to reduce load on the transformer that is going on more. And faced with the values of short circuit current in the group entering before and after the transformer. This study referred to IEC 354 in 1972.} }