@thesis{thesis, author={IZZUDDIN FEBRI and Pahiyanti Novi Gusti}, title ={PERBANDINGAN RUGI DAYA PADA SAMBUNGAN PENGHANTAR JARINGAN TEGANGAN MENENGAH 20 KV ANTARA PARALLEL GROOVE DAN LIVE LINE CONNECTOR DI PENYULANG GM SITUT 1 SINGKAWANG}, year={2018}, url={http://156.67.221.169/719/}, abstract={To get the quality of the distribution system optimal feeder GM Situt 1 in PLN Area of Singkawang done a comparison of power loss on the connection conductor of a medium voltage network 20 kV between the Parallel Groove and the Live Line Connector (LLC). Can in the analysis of the results of the comparison between the second connection such that in the measurement on the pole LBS aneka sari, LBS Kirdasana and LBS the SSA at feeders GM Situt 1 in which the measurement is performed because at the feeder GM Situt 1 there is a 6 point repairs/maintenance to determine the results of the comparison. The analysis of obtained get the conclusion that the measurement at the point of LBS the SSA for Parallel Groove flow amounted to 68,1 A voltage of 18,719 kV and cos Ø of 0,911. While the measurement after using the connection of the Live Line Connector (LLC) at the LBS the same obtained value of the current of 61,7 A, a voltage of 18,987 kV and cos Ø of 0,950. The second connection has a power loss in the produce of the Parallel Groove of 15,1142 kW and the Live Line Connector (LLC) of 12,4967 kW for the results of the measurement at the point of pole LBS SSA, Kirdasana and Aneka Sari. The difference in power loss from the overall results of the comparison of both the connection of 2,6175 kW.} }