@thesis{thesis, author={Budi S Purnomo Willy and Wibowo Azrul Tri}, title ={ANALISA RUGI-RUGI DAYA JARINGAN TEGANGAN RENDAH STUDI KASUS GARDU DISTRIBUSI RJ 0020 RJ PT. PLN (PERSERO) RAYON RASAU JAYA PONTIANAK KALIMANTAN BARAT}, year={2018}, url={http://156.67.221.169/851/}, abstract={A good electric power system should have a voltage value that does not exceed the tolerance limit and small power losses. The tolerable limit for a voltage value based on SPLN 1 of 1995 is + 5% to -10% of the nominal voltage while the power losses are kept as small as possible to reduce losses. Due to the impedance of the channel and the load, the value of the voltage at the sender side will not be equal to the value of the voltage at the receiver side. In this thesis discussed the loss of power on the distribution substation RJ 0020 RJ has two majors, with the burden is a household customer. From the calculation results manually obtained power losses on the distribution of RJ 0020 RJ Distributor of the department 1 of 5,9% and the majors 2 of 4,5%.} }