DETAIL DOCUMENT
PERANCANGAN INSTALASI SISTEM PENGGERAK MESIN AGITATOR PADA REAKTOR PROSES OKSIDASI DI PT. INDORAMA PETROCHEMICALS CILEGON
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Paradi, Moh. Aziz
Budiman, Masgunarto
Subject
Teknik Elektro 
Datestamp
2019-11-05 00:32:30 
Abstract :
Nowadays almost all transportation and production industries use driving machine especially electric driving machine. The electric drive system consists of motors, power circuits, and control circuits that control motor movement. In designing the driving system, it is necessary to know the load requirements to be driven, the environmental conditions in which the electrical installation will be installed and the potential danger that may threaten it and must comply with the applicable electrical installation standard (PUIL) in order for the electrical installation are mounted securely, reliably, and environmentally-friendly. The choice of an oxidation reactor agitator drive system using an alternating current system with frequency regulation, using a motor with a power of 1150 kW and a protection index code is IP56, as well as to protect people from the dangers of indirect touch, the installation grounding resistance shall not exceed 0,00339 ?. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara