DETAIL DOCUMENT
ANALISIS EFEKTIVITAS GENERATOR STATOR COOLING WATER TERHADAP RUGI-RUGI DAYA YANG TIMBUL PADA STATOR GENERATOR UNIT 1 PLTU LONTAR
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Muttaqin, Muhammad
Widyastuti, Christine
Subject
Teknik Elektro 
Datestamp
2022-11-01 07:36:37 
Abstract :
In everyday life, electricity is a major need that is widely needed and utilized by humans. Electrical energy is produced by a device called a generator, where the generator is a synchronous machine that converts mechanical energy into electrical energy. Because electrical energy is needed all the time, making the generator work continuously results in power losses, one of which is the loss of stator power. Stator power loss will make the temperature in the stator higher, so a cooling system is needed, namely the generator stator cooling water (GSCW). The cooling system will keep the stator temperature within its standard so that the generator can work efficiently. Based on the results of the research, generator unit 1 PLTU Lontar. obtained at a minimum load of 03:00 with an active power of 171.87 MW, a stator power loss of 178.67 kW, and a water cooling effectiveness of 93.51% at 44.58 ° and a calculation temperature of 41.69 ° At the maximum load at 12:00 with an active power of 292.73 MW, the stator power loss is 430.12 kW and the water cooling effectiveness is 97.90% with an actual temperature of 51.95 C° and a calculation temperature of 50.86 C°. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara