STUDI INDEKS KEANDALAN SISTEM DISTRIBUSI 20 KV PADA PENYULANG HOTE DI PT.PLN (PERSERO) ULP BULA KABUPATEN SERAM TIMUR
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Rumau, Ismail
Hidayat, Syarif
Subject
Teknik Elektro 
Datestamp
2022-11-01 08:31:00 
Abstract :
The distribution system as one part of system power electricity and is directly related to consumers. The distribution system is one part of PLN that most often experiences interference or damage in the electric power system, therefore it is very important to always maintain the reliability of electric power in order to continue to provide maximum service to consumers. The reliability of an electric power system is very important to be maintained in order to meet consumer needs. In this study, the method used was a descriptive quantitative method. The results of the data analysis obtained are the SAIDI value of 5,114 hours / customer / year (2020), 4,174 hours / customer / year (2021). SAIFI of 4,878 outages/customers/year (2020), 1,991 outages/customers/year (2021). CAIDI is 15,820 hours/subscriber (2020), 44,951 hours/subscriber (2021) and ASAI 11,988 (2020), 7,989 (2021). Several factors have led to the lack of reliability of hote refiners in PT. PLN (Persero) ULP Bula, Eastern Seram Regency, such as Fallen Trees, Bats, Snakes, Tree Branches and others. then the steps taken to improve reliability are routinely rambasan, complete pole climbing, FCO installation, and installation of nets on poles to prevent wild animals such as snakes and others. 