DETAIL DOCUMENT
ANALISIS PENGARUH POLUTAN DEBU DAN GARAM TERHADAP ISOLATOR PORSELEN DAN ISOLATOR KACA
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
FIQIH NURWAHID, MUHAMMAD
Christiono, Christiono
Subject
Teknik Elektro 
Datestamp
2022-11-03 02:21:48 
Abstract :
In this study aimed to determine the influence of salt pollutants and soil dust on porcelain insulators in mountainous areas, the methods used in this study were discharge testing and breakdown testing of insulators porcelain patterned with soil dust and temperature state around the test equipment. Based on the results of this study, the massof different pollutants can affect the value of the discharge voltage and the value of the voltage breakdown voltage. Mass of dust pollutants and salt is carried out by firstweighing the mass of soil dust pollutants and salts that want to be given to porcelain insulators, porcelain insulators in pollutants with 4 samples, 25 grams, 50 grams, 75 grams, 100 grams The results on the insulator test with 25 gram soil dust polluted were 73,57 kV and in the first test with 50 gram soil dust pollutant the results were 67,64 kV, the decrease that occurred when the pollutant was present was 6%, it can be concluded from the test results that The more insulators exposed to pollutants, the lower the breakdown voltage and discharge test voltage values 
Institution Info

Institut Teknologi Perusahaan Listrik Negara