The more demand for electrical energy, the more the equipment at Rasuna's garden
substation will increase. A power transformer is a device that really senses the increasing
temperature of the conductor in the form of a transformer winding. Therefore the
transformer has insulation inside in the form of cellulose paper and transformer oil. To
find out indications of failure in the transformer, we can test one type of insulation on the
transformer, namely transformer oil. Where. By way of testing DGA and testing the
Translucent Voltage of Transformer Oil. After testing the DGA by analyzing the test
results using the TDCG method with 770.0 ppm produced, the Key Gas method with the
results of H2 3.67%, CH4 16.28%, C2H6 36.81%, C2H4 2.822% , C2H2 0%, CO
39.08%. The average temperature of the transformer before being obtained is 33.02?
and after it is obtained 58.2?, which means the temperature after is cooler than before
maintaining the PM22D type transformer. Therefore, maintenance is carried out on the
transformer by observing the measurement of the load where in this maintenance it is
measured whether there are losses that occur, and also how to balance the load so that the
transformer can work normally again.