ANALISIS PENGARUH KANDUNGAN AIR TERHADAP TEGANGAN TEMBUS PADA MINYAK TRANSFORMATOR MENGGUNAKAN METODE KORELASI
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Hafizh Surya Kusumah, Muhammad
Diantari, Retno Aita
Subject
Teknik Elektro 
Datestamp
2022-11-04 02:23:33 
Abstract :
Transformer oil is one of the insulating and cooling media contained in the transformer. As an insulator medium must be able to separate the active parts with different phases. In the isolation of transformer oil, there will be changes if there is impureness contained in the oil. This will accelerate the occurrence of the isolation failure process. There are several factors that can influence the occurrence of insulation failures including the presence of solid particles, water vapor and gas bubbles. The water content can reduce the electrical resistance of transformer oil and cause ionization, which damages the solid and liquid insulation. This test aims to determine the value of the penetrating voltage and dielectric strength in Nynas and Hyrax oils with different compositions of water content. Then to find out how the ratio of the penetrating voltage and dielectric strength in Nynas oil and Hyrax oil with different water content compositions. To achieve the objectives in this test, it uses a correlation analysis method, in order to find out how the relationship between the translucent voltage ratio and the water content. So the more water content mixed or contained in transformer oil the BDV (Break Down Voltage) value and the dielectric strength will be the smaller the nature of the 