DETAIL DOCUMENT
Analisa Pengaruh Suhu Dan Polutan Abu Arang Terhadap Tegangan Tembus Isolator Porselen 20kV
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Ridho Wicaksono, Gian
Yogianto, Aloysius Agus
Subject
Teknik Elektro 
Datestamp
2022-11-07 03:08:10 
Abstract :
This research was conducted to determine the quality and resistance of solid porcelain insulators by testing the breakdown voltage which is influenced by temperature and pollutants. The purpose of this study is to determine the effect of temperature and pollutants on the breakdown voltage of 20kV porcelain insulators. The method used in this research is the experimental method of testing the breakdown voltage in the High Voltage Laboratory. In this study, the Air correction factor was used to obtain a standard breakdown voltage. From the results of the study, it was found that when the temperature variable increased, even though there were variations, the breakdown voltage of the insulator increased, the highest value at 38ºC was 91.12kV, while the lowest at 30ºC was 84.15 kV. With the pollutant mass variable, when the pollutant mass increases, the breakdown voltage of the insulator is reduced, at a pollutant mass of 30 grams the breakdown voltage is 75.49 kV and with a pollutant mass of 150 grams the breakdown voltage is 61.22 kV. With the increase in pollutant mass and temperature variables, the breakdown voltage value decreases because the pollutant has an effect on decreasing the breakdown voltage value, at 30 gram pollutant mass it is 75.04 kV, and with a pollutant mass of 150 grams it is 63.11 kV 
Institution Info

Institut Teknologi Perusahaan Listrik Negara