DETAIL DOCUMENT
IMPLEMENTASI SECTION TECHNIQUE UNTUK KEANDALAN PADA PENYULANG BENDUNGAN DI PT. (PERSERO) PLN UP3 KEBON JERUK
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
SELVINA GULTOM, FEBIOLA
Damiri, Dhami Johar
Subject
Teknik Elektro 
Datestamp
2022-11-07 03:28:34 
Abstract :
Calculating electrical system reliability is important because it determines the quality and availability of power service to customers. With 60 dam feeder failures in 2021, the reliability indicators need to be analyzed. This study uses a quantitative approach by means of correlation studies. The calculation method used, i.e. that of the section method, has the advantage that it is a simple calculation and the parameters used are continuous and instantaneous failure rates, making the final result of this method more accurate in the field. increase. Based on the calculated results, the dam feeder reliability in 2021 is SAIFI value of 1.350797 failures/year and SAIDI value of 4.404207578 hours/year. Comparing this value with SPLN No. 59 of 1985, we can say that SAIFI feeders are unreliable and SAIDI feeders are reliable. In order to improve the value of the reliability index of the distribution system, regular maintenance or service can be carried out to operate the distribution network equipment safely, reliably, effectively and efficiently, and to enhance the reliability of distribution. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara