DETAIL DOCUMENT
ANALISIS SUSUT UMUR TRANSFORMATOR DISTRIBUSI AKIBAT PEMBEBANAN LEBIH DI PT.PLN (PERSERO) UNIT LAYANAN PELANGGAN OESAO
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Agus Widanta,, I Gede
Pasra, Nurmiati
Subject
Teknik Elektro 
Datestamp
2022-11-07 07:53:54 
Abstract :
The transformer is an important component of the distribution system because it acts as a load regulator using the principle of electromagnetic induction by converting electrical energy from one circuit to another through magnetic coupling. The factor that causes loss of life of the transformer is loading. Distribution Transformer with substation code 43180KR047 with a peak load of 28% obtained a daily life loss of 6.72 hours, so that the remaining life of the Transformer is 18.59 years. Distribution Transformer with substation code 43180KR065 with a peak loading of 33%, the age loss per day is 7.24 hours, so the remaining life of the transformer is 18,24 years. Distribution transformer with substation code 43180KR076 with a peak load of 18.83%, the age loss per day is 4.52 hours, so the remaining life of the transformer is 19,42 years. The higher the load on a transformer, the value of life shrinkage will also be greater. The increase in ambient temperature will affect the magnitude of the increase in the hot spot temperature, the higher the value of the ambient temperature, the hot spot temperature will also be greater as well as the value of the reduced life of the transformer. The higher the load on the transformer, the value of life shrinkage will be greater and the remaining life of the transformer will be smaller. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara