DETAIL DOCUMENT
PERANCANGAN GROUNDING CALCULATION PADA GARDU INDUK 70 kV LABUAN BAJO EXTENSION DI PT PLN UNIT INDUK PEMBANGUNAN NUSA TENGGARA
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
SATYA PUTRA P, TRI
Diantari, Retno Aita
Subject
Teknik Elektro 
Datestamp
2022-11-07 08:13:05 
Abstract :
Substations in the electricity system are part of a system or subsystem that functions to transmit voltage from a high voltage level to a lower voltage level. Equipment at the Substation installed in the Switchyard consists of the main and supporting materials/equipment or accessories. The grounding system is part of the electric power system which has the function of distributing to the ground in the event of a voltage or overcurrent charge to minimize the disturbance caused, consisting of a grounding mesh and a grounding rod which in determining the design is based on the maximum value of step voltage and touch voltage. namely the voltage difference between the GPR (Grounding Potential Rise). Based on the calculation results, the GPR value is 3318.9 so it is necessary to calculate the touch stress and step voltage. The 70 kV Labuan Bajo Extension 30 MVA substation grounding system with a combination model of grid and rod has been based on the IEEE Std 80-2013 standard with the calculation of the touch voltage which is 530.18 V smaller than the permitted standard of 1581.9 V, voltage step, which is 314.73 V, which is smaller than the permitted standard of 5661.3 V. Based on the layout design of the substation and grounding calculations, it can also be determined the Bill of Quantity from the grounding installation work at the 70 KV Labuan Bajo Extension substation. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara