ANALISA DESAIN DAN PEMASANGAN DIRECT TRANSFER TRIP SEBAGAI PERKUATAN DEFENSE SCHEME SISTEM TIMOR
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
AFFANDI, M MAWAHIB
Purwanto, Sugeng
Subject
Teknik Elektro 
Datestamp
2022-11-08 01:15:59 
Abstract :
Frequency is one indicator that represents the quality of electric power. The system frequency describes the balance between the active power (MW) of generation and the active power (MW) consumed by the load. Based on historical data of disturbances record in the Timor Grid System, mostly if there is a disturbance in the 70kV BolokMaulafa SUTT two lines simultaneously, it will result in a blackout. This is because the 70kV Bolok-Maulafa SUTT carries 75% of the system load, thus causing the system frequency balance to not be achieved. In the research that has been done, it was found that to overcome these problems, a DTT (Direct Transfer Trip) method is needed, namely a trip command scheme to 2 PLTU units when there is a disturbance in the 70kV Bolok-Maulafa SUTT two lines simultaneously so that frequency stability can be maintained and the system doesn?t blackouts. 