ANALISIS PENYEBAB KEGAGALAN BACA DATA DAN KELAINAN METER PELANGGAN AUTOMATIC METER READING (AMR) MENGGUNAKAN APLIKASI AMICON DI PT PLN (PERSERO) UP3 SUMEDANG
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
PUSPA ERVIRA, LILIS
Purwanto, Sugeng
Subject
Teknik Elektro 
Datestamp
2022-11-08 01:34:21 
Abstract :
PLN's KWh meter is a tool to measure the amount of electricity used by customers and as a reference for electricity bills that must be paid by customers every month. The recording of customer meter booths, especially AMR meter customers, uses the Centralized Automatic Meter Reading (A2MRT) Application. Sometimes there is a problem that AMR cannot send data to the server or it fails to read. From these problems, tools, methods and analysis of AMR data read failures are needed so that the causes can be mapped and followed up quickly and precisely. The tools used are AMICON which functions as a Centralized AMR system and is implemented in the PLN distribution unit environment. The research method used is a quantitative method by collecting data from the 2021 AMICON reading results at PT PLN (Persero) UP3 Sumedang. The results obtained, the cause of the AMR meter failing to read as much as 55.33% due to damage to communication devices (Modem, Antenna, Simcard, Cable), 4.92% due to damaged meter equipment, 5.94% due to faulty adapter and 33.81% due to asynchronous AMR data with DIL AP2T. Abnormalities that occur in the AMR kWh meter include reverse wiring, unbalanced currents and deviations due to metering equipment damage which are analyzed using load profile parameters, phasor diagrams and EIS as the basis for calculating a Supplementary Bill. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara