OPTIMALISASI KEANDALAN SISTEM DISTRIBUSI 20 KV DI PT PLN (PERSERO) UP3 KENDARI DI PENYULANG TIELINE POMAALA
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
CABRINY, MOENICA
Azzahra, Septianissa
Subject
Teknik Elektro 
Datestamp
2022-11-08 01:56:35 
Abstract :
An electric power system has a benchmark to measure the level of reliability of the network that delivers electrical energy to the load continuously, namely the SAIDI & SAIFI reliability index. Therefore, optimization of reliability is needed to be able to find the best value of a reliability index obtained from evaluation and improvement activities on target. From the results of the analysis through the Tableau software, the feeder that did not meet the IEEE P1366-2003 standard was the Tieline Pomaala feeder with the achievement of SAIDI 2.59 hour/plg/year and SAIFI 1.73 times/plg/year. The result of further evaluation, equipment Recloser/PMCB became the second largest contribution so that it was followed up by recalculating the coordination of protection and simulation. After the perfect adjustment of protection coordination, the data shows a decrease in SAIDI & SAIFI on the Tieline Pomaala Feeder in 2022 Recloser/PMCB equipment to zero 0 minutes/plg/year and 0 times/plg/year, from the previous year 2021 contributed 22.2 minutes/ plg/year and 0.191 times/plg/year 