EVALUASI KONDISI DAN KELAYAKAN OPERASI PERANGKAT HUBUNG BAGI TEGANGAN RENDAH (PHB-TR) GARDU KLD 133 PT. PLN (PERSERO) UP3 SERPONG
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
PANTOW, KEZIA CLAUDIA
Yogianto, Aloysius Agus
Subject
Teknik Elektro 
Datestamp
2023-06-12 07:45:49 
Abstract :
The Low Voltage Connection Device functions is as adivider and protection in electric currents. In this case, there was a Low Voltage Device that get fire due to a loose connector on the safety components. After it get fire, the authorities had taken care of it temporarily by only replacing the protection of NH Fuse rail, and then the Low Voltage Device was operating again. However, by the condition, the other components are also damaged too, so it should not be operating anymore. Based on this case, there will be evaluation of the condition in each components in Low Voltage Connection Device which still operating to see its operational feasibility. The purpose is to determine the condition of the Low Voltage Device after burning, determine the suitability of the components installed on it with the standards used, determine the suitability of NH Fuse rating, and determine the operational feasibility of the Low Voltage Device after burning. Using the direct observation method to collect data by visual inspection to check the conditions and check the suitability of installed components by standard SPLN D3.016-2013. The evaluation result, the condition of the LV Device is damaged, most of it is charred, blistered, cracked, melted, dented, and peeled off on the surface of the components which can cause and disruption, although the suitability of the components installed in the field is mostly still in accordance with standards. Under these conditions the Low Voltage Device should not be operated again, so it can be said that it is not feasible to operate. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara