ANALISA KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN SUSUT PADA TRANSFORMATOR DISTRIBUSI DI PT PLN (PERSERO) UP3 SEMARANG
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Wicaksono, Agum
Hutadjulu, Albert Gifson
Subject
Teknik Elektro 
Datestamp
2023-06-16 08:04:28 
Abstract :
The target for network losses in 2022 at PT PLN (Persero) UP3 Semarang is 8%. However, the achievement of losses in October only reached 10.04%. So it is necessary to reduce losses so that the target of 8% can be achieved. One way to do this is to do load balancing. Balancing is done by exchanging the phases on the PHB-TR. Based on the calculation results, the imbalance at the RJLS substation: 33%, RJKS: 5% and MAI: 34%. After balancing it decreased to RJLS: 16% and MAI: 6%. The neutral current at the RJLS and MAI substations before balancing RJLS: 22.54A and MAI: 2.69A, after balancing it drops to RJLS: 9.54% and MAI: 11.53%. Losses caused by the transformer neutral current before balancing RJKS: 350.5 W and MAI: 3645.8 W, after balancing decreased to RJLS: 62.7 W and MAI: 91.7 W. Losses due to current flowing to the ground before balancing at the RJLS 1049.7 W and MAI 4651.2 W substation. After balancing, it drops to RJLS 538.2 W and MAI 1253.1 W. Energy losses in percent before balancing at the RJLS substation 8.3 % and MAI 26.78%. After balancing it decreased to 3.5% RJLS and 4.2% MAI. The conclusion obtained is that balancing the load using the phase swapping method on the PHB-TR can reduce the value of unbalance and neutral currents, so that losses can decrease. 