Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Septian, Ferrizal Nurli
Kurniasih, Novi
Subject
Teknik Elektro
Datestamp
2023-11-01 07:28:29
Abstract :
PLN builds electricity transmission lines, especially overhead transmission lines, which
is planned with government programs in accelerating the supply of electricity to the
multitude citizen. Electric field and magnetic field, known as electromagnetic field, are
generated by the presence of electrical transmission line. Problems arise regarding
customer complaints about the influence of electromagnetic field Sanggau ? Sekadau
high-voltage 150 kV overhead transmission line, so that evidence is needed to convince
wider society, especially below the transmission line. The research method used is a
quantitative experimental method by carrying out direct measurements below 150 kV
overhead Sanggau ? Sekadau transmission line. Measurements were made using the EMF
tester GQ EMF-380 V2. Research results showed magnetic field measurement value was
0,17 µT to 0,37 µT or 0,17% to 0,37% below the permissible exposure limit standart
(100 µT ) and the electric field value was 1 V/m to 1025 V/m or 0,02% to 20,5% below
the permissible exposure limit standart (5 kV/m). In residential house the percentage
value of the magnetic field is 0,32% and the electric field is 7,36% below the permissible
exposure limit standart. The difference in measurement results due to the influence of the
ground surface, and the presence of surrounding objects such as trees, it is found that
trees can absorb magnetic field value of 0% to 52,9% and electric fields of 18,6% to 99,9
%.