Analisa Perbaikan Losses Akibat Beban Tidak Seimbang pada Jaringan Tegangan Rendah dengan Metode Pecah Beban
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Sari, Rakhma Yunita
Pramoono, Tri Joko
Subject
Teknik Mesin 
Datestamp
2019-10-28 04:27:54 
Abstract :
K42N substation have assesment 37,49% wih flow unbalance for improvement use load breakdown method This analysis based on the need for improvement of voltage profile on low voltage system at K42N substation in Cempaka Putih Area which experienced unbalance load. The method chosen to improve the voltage profile is the load breakdown method which is done by equalize the load on feeder at the K42N substation and increase one feeder on the K42N substation. By making this analysis it is known that system losses decreased from 4,49705 kW to 0,82465 kW and the voltage drop on the K42N substation also decreased difference in value 12,7061% 