Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Tambun, Ra Crystal S. P.
Ispranyoto, Edy
Subject
Teknik Elektro
Datestamp
2019-10-28 04:28:34
Abstract :
Operation of power transformer at a substation is never separated from interference, both short circuit on phase-phase or phase-neutral; same thing is also happening in Karet Baru GIS. Disruptions that occur can cause losses on
the part of consumers of electrical energy, more over Karet Baru GIS is one of the suppliers for VIP consumers. Therefore, it is necessary to coordinate protection instrument on the outgoing dan incoming of transformer so that
interference can be minimized as small as possible. Over current relay is preffered to be used to detect short-circuit between two phases; and ground fault relay is preffered to be used to detect short circuit a phase and neutral.
The short circuit current which is happened over the current setting, on over current relay the current setting for outgoing is 2,25 Ampere and for incoming is 4,503 Ampere while in the ground fault relay the current setting for outgoing is
0,41 Ampere and for incoming is 0,205 Ampere triggers the over current relay and ground fault relay which works with the applied time setting so these can avoid the risk of damage to the electrical system.