Abstract :
Load unbalance in the electric power distribution system occurs because the use of uneven load on each phase that is in the secondary side of the transformer. In the Tanjung Priok area is the a heavy use of loads with industrial sites and densely populated settlements, so that the time spent using unequal loads by each consumer causes a load unbalance. As a result of this unbalance will a cause currents in the neutral transformer. However, due to the emergence of neutral currents in the neutral conductor causing losses that affect the transformer. Efficiency of KG 72 LWBP substation 99.24% and 98.88% WBP, for LWBP KG 162 substation 97.85% and 96.44% WBP. In this study obtained the percentage value of the unbalance taken outside the peak load time and peak load time at 72 and KG 162. KG substations at KG substation 72 kwh losses obtained at 30.75 LWBP and 10.79 WBP for 162 LWBP KG 120.32 kwh , at WBP 35.77, with the percentage of unbalanced data the LWBP load on the 72 KG substation is 6% and WBP 20.3% and at LWBP 162 KG Substation 11.6% and 22.6% WBP. Losses in conductor neutral substation KG 72 LWBP 1,537 kW and WBP 2,697 kW . For Substation KG 162 LWBP 6,016 kW and WBP 8,944 kW. 