ANALISIS DAMPAK KETIDAKSEIMBANGAN BEBAN TERHADAP ARUS NETRAL DAN RUGI-RUGI PADA JARINGAN TEGANGAN RENDAH
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Sulistiani, Nandiyah
Prianda, Prianda
Subject
Teknik Elektro 
Datestamp
2019-10-28 04:34:27 
Abstract :
Load imbalances in the electric power distribution system always occur and the cause is the use of electrical energy by customers that are not always the same and evenly used. As a result of the load imbalance, it causes a neutral conductive current in the transformer. This neutral current causes losses. In this thesis, the author uses a vector and mathematical addition method which includes equations of transformer load imbalances, power losses and transformer efficiency. The author also includes a reconnection method for equalizing the distribution of the load of the Low Voltage Network (JTR) as an effort to minimize load imbalances. After being analyzed, it was found that the greater the value of the load imbalance, the more neutral current flowing will be. In the MK224 distribution transformer the load imbalance at LWBP is 20.73% and at WBP 28.06% creates a neutral current of 255.688 Ampere at LWBP and 361.748 Ampere in WBP causing losses of 20.95828 kW on LWBP and 1, 91808 kW on WBP. 