KAJIAN DROP TEGANGAN PADA JARINGAN DISTRIBUSI TEGANGAN MENENGAH FEEDER R6 RAYON TENGGARONG
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Bougari, Rivaldy Septa
Willy B.S, Purnomo
Subject
Teknik Elektro 
Datestamp
2019-10-28 04:35:41 
Abstract :
This final project aims to determine the value of the voltage drop that occurs along the JTM feeder R6, then fix the voltage drop and analyze the factors that influence the occurrence of voltage drop in JTM feeder R6. The analysis of the voltage drop that occurs in the R6 feeder can be considered as a feasibility by PT PLN (Persero) Rayon Tengon for the development of JTM if there are additional burdens in the future. The method used in the voltage drop evaluation study is the documentary / literature method, interview and observation. Then with this method data processing is performed and the results of the calculation of voltage drop and the factors that influence the voltage drop are obtained. The send voltage on the R6 feeder is measured directly at 20,771 Volt. Based on the research results, the value of the received voltage at the end of the R6 feeder is 19537.52 Volt (5.93%) under real load conditions, 19919.99 Volt (4.1%) assuming the distribution of load substations is 60% and 19636,35 (5.46%) assuming the distribution of load substations is 80%. Voltage drop occurs due to several factors, including channels too long, small cross-sectional area, large impedance values and the amount of load value. 