RUGI – RUGI PADA PENGHANTAR NETRAL AKIBAT KETIDAKSEIMBANGAN BEBAN TRANSFORMATOR GARDU DISTRIBUSI SP277 DAN KJ352 PT.PLN AREA KEBON JERUK
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Aditiya, I Putu Gede Putera
Ispranyoto, Edy
Subject
Teknik Elektro 
Datestamp
2019-10-28 09:17:32 
Abstract :
The imbalance of the distribution transformer load is caused by uneven load spread on each phase of the secondary side of the transformer, So as to cause the current to flow in the neutral conductor, which means it is a losses (I2.R) on the neutral conductor. The magnitude of this losses in the neutral conductor depends on the amount of current and the conductor resistance. This research aims to find out how big imbalance in distribution substations of SP277 and KJ352, amount of loss and then converted into rupiah. This research uses a vectorist method to analyze the losses on neutral conductor of low voltage system. After being analyzed on SP277, the load imbalance was 7,48% (LWBP) and 4,23% (WBP) with losses of 182,68 kWh (WBP) and 27,86 kWh (WBP). And the KJ352 substation 12,90% imbalance (LWBP) and 23,35% (WBP) with losses 42,76 kWh (LWBP) and 18,12 kWh (WBP). 