DETAIL DOCUMENT
Kajian Jatuh Tegangan Pada Penyulang Ajar PT.PLN (PERSERO) Area Cikokol Tangerang.
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Armando, Adam
Budi S, Purnomo Willy
Subject
Teknik Elektro 
Datestamp
2019-10-30 07:37:32 
Abstract :
Distribution of electric power substations (GI) to Distribution Substation (GD) must have a voltage loss received by the distribution substation especially the medium voltage. The development of the industry today is increased which will certainly affect the use of electrical loads, so that the stability of the power system is always needed to costumer. The purpose of this study was to knowing the magnitude of the voltage drop that occur in the primary line distribution Ajar. The result of drop voltage in the primary line distribution Ajar can be used as consideration of feasibility by PT PLN (Persero) Cikokol Area for development or addition of burden in the future. Result obtained. At Normal load of 50% substation use of 2.02% while at full load condition at 80% is 4.04%. The value if the voltage drop is good under normal load and full load conditions who still meet the large standard voltage drop set by PT PLN (Persero) on SPLN No.72 of 1987 ie the allowable voltage drop is 5% of working voltage. 