Analisis Kegagalan Isolasi Akibat Partial Discharge Rongga Pada Kabel tanah XLPE 20 kV
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Wijayanto, Trianto Desti
Sudibyo, Uno Bintang
Subject
Teknik Elektro 
Datestamp
2019-12-05 12:43:31 
Abstract :
With the benefits that?s ground cable can offer besides air channel power line makes a growth demand of ground cables in Indonesian market places. Trouble comes up when the product of the ground cables have a bad quality that makes financial loss for the company. This research goal is how to declare a ground cable is qualify enough to pass. Partial discharge of a ground cables is affected by quantity and quality of a void in the insulation of the cable. On this thesis discuss about void partial discharge on the ground cable 20 kV. Partial discharge method that use in this research is a conventional direct coupling method that include in IEC 60270 standard about high voltage measurements. For partial discharge measurement value is maximal 5 pC. From the result of research there is two comparison of the ground cable, the good quality of ground cable has a partial discharge value about 3.7 pC while the bad quality of ground cable has a partial discharge value about 28.3 pC. And from the calculation of the void partial discharge, it can be concluded that the value of the partial discharge is directly proportional to the cavity in the ground cable insulation. 