Implementasi Teknologi Blocking Autoreclose pada Jaringan Transmisi Hybrid
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Zulham, Muhammad
Arifin, Zainal
Subject
Teknik Elektro 
Datestamp
2022-11-30 06:31:26 
Abstract :
The continuity of electricity in the transmission system becomes very important in maintaining the reliability of electricity supply. Autoreclose function in the transmission system is one of the patterns in maintaining system reliability. At present there are several 150kV transmission networks which are hybrid transmission systems, namely a combination of Cable-Overhead transmission lines. Temporary interruption on this hybrid transmission network will cause outages if the protection scheme is not equipped with autoreclose. Autoreclose is set to work when a disturbance in the Overhead Line (OHL) section and does not work (blocking) when interference on the Underground Cable (UGC) section. Application of blocking autoreclose technology in hybrid transmission networks by utilizing configurable / programmable protection zones on distance relays, as well as the use of optical CT or Non Conventional Instrument Transformers (NCIT) as current sensors for CCP relays installed on cable lines with distances certain because it cannot be accessed by conventional CT to be the solution in this thesis. 