Abstract :
Along the transmission line, there are no outside or internal influences that
can cause interference with the transmission line. One of the internal influences that
can cause interference is the occurrence of hotspots. To detect hotspot anomalies,
thermovision activities are carried out with thermovision activities and become a
reference for corrective maintenance follow-up. If the hotspot is left unchecked, it
will experience losses and will have an impact on damage to high-voltage
equipment and transmission systems. For this reason, it is necessary to immediately
repair hotspot anomalies with Live Line Maintenance (PDKB) in order to avoid
energy losses, mechanical failures and electrical failures in the distribution system.
In this study using quantitative and descriptive methods. The results of
thermovision data on the 150kV Pelabuhan Ratu ? Semenjawa SUTT detected 2
hotspot points based on the calculation of the temperature difference at the
maximum load (?T) on tower C.03-C.02 Phase S with ?T 55.76°C and tower C.61-
C.62 Phase R with ?T 61.3°C. Hotspot anomaly mitigation is carried out by
cleaning jumper terminals in towers C.03?C.02 Phase S and adding conductors with
PG clamps on towers C.61?C.62 Phase R. The losses received due to hotspot
anomalies (in rupiah) in 6 months (1 Semester of Performance) for 900VA power
household customers amounted to Rp.3,853,605.6, 1300VA 2200VA power
customers amounted to Rp.4,117,828, 38 and 3500VA power customers and above
amounting to Rp.4,758,661.32.