DETAIL DOCUMENT
ANALISIS SHIELDING DENGAN PEMODELAN ELEKTROGEOMETRI PADA GARDU INDUK TEGANGAN EKSTRA TINGGI GANDUL
Total View This Week0
Institusion
Institut Teknologi Perusahaan Listrik Negara
Author
Ramana, Randa
Soewono, Soetjipto
Subject
Teknik Elektro 
Datestamp
2019-11-05 00:32:02 
Abstract :
Direct lightning stroke in an extrahigh voltage (EHV) substation might cause temporary to permanent disruption in a form of equipment breakdown. Therefore, a reliable shielding system is required in order to protect substation?s equipment from direct stroke. Electrogeometric Model(EGM) is one of several shielding system modeling that is considered reliable. It is also a standard modeling to design a shielding system in power system structures such as, transmission lines, distributions, and subtations. In this research, Revised EGM is being used to analyze the shielding system installed in Gandul EHV substation. Despite of the existance of 15.48% hazardous stroke current, shielding system of Gandul EHV is considered reliable due to the length of expected period between equipment failure due to lightning stroke, which is 1637 years. 
Institution Info

Institut Teknologi Perusahaan Listrik Negara